Which span condition
A single span between two supports is simply supported, the conservative case. A long straight run over many supports behaves closer to a continuous beam, which allows a longer span. Real practice uses the simply supported value or a factor between the two.
Sag and drainage
A sag limit of about 2.5 mm (0.1 in) is common to avoid pockets that hold liquid in gas lines or condensate in steam lines.
Assumptions and limits
- Uniformly distributed load.
- No concentrated loads, wind or seismic.
- Linear elastic beam behaviour.
References
- MSS SP-58, Pipe hangers and supports.
- ASME B31.1 Table 121.5 suggested support spacing.
- Roark's Formulas for Stress and Strain, beams.
Questions
- Why is the hydrotest case important?
- Gas lines are tested with water, so supports must carry the water-filled weight during testing even if the line normally carries gas.
- What allowable stress should I use?
- Many designers limit weight stress to around 30 to 40 MPa for carbon steel so that pressure and thermal stresses still fit within code limits.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.