Which resistance controls
The largest resistance dominates U. If the outside film is 60% of the total, doubling the inside coefficient barely helps. Look at the percentage breakdown in the working before changing tube material or velocity.
Fouling
Fouling factors are design allowances for deposits. Typical values are 0.0001 to 0.0002 m²K/W for treated cooling water and clean process fluids, and 0.0003 to 0.0009 for river water, heavy oils and dirty services. Over-generous fouling factors make exchangers unnecessarily large.
Assumptions and limits
- Cylindrical tube, outside-area basis.
- Steady state with constant properties.
References
- TEMA Standards, fouling resistances.
- Kern, D. Q., Process Heat Transfer.
- Incropera and DeWitt, Fundamentals of Heat and Mass Transfer.
Questions
- Why is U lower than both film coefficients?
- Resistances add in series, so U is always below the lowest single coefficient.
- Does tube material matter much?
- Usually little, because the wall resistance is small. It matters more for thick-walled, low-conductivity tubes such as titanium or stainless with high film coefficients.