The correction factor F
A shell-and-tube exchanger with two tube passes is partly counter-flow and partly parallel-flow, so its effective temperature difference is lower than the counter-flow LMTD. F expresses that loss. Designs below about F = 0.8 waste area and are unstable to small changes in temperature, so add shells in series instead.
Choosing U
U depends on the fluids, velocities, tube material and fouling. Typical clean values are 800 to 1500 W/m²·K for water to water and 200 to 500 for water to light oil. Use the overall U calculator to build U from film coefficients and fouling factors.
Assumptions and limits
- Constant U and specific heats along the exchanger.
- No phase change unless the duty already accounts for it.
- F from the standard 1-2 exchanger equation.
References
- Kern, D. Q., Process Heat Transfer.
- TEMA Standards, mean temperature difference correction.
- Incropera, F. P. and DeWitt, D. P., Fundamentals of Heat and Mass Transfer.
Questions
- What does R = 1 mean?
- Both fluids have the same heat capacity rate. The formula has a special limit there, which the calculator handles.
- Should I add a margin?
- Most designers add 10 to 25% area for uncertainty in U and fouling, unless fouling is already included in U.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.