Calorifier Heat-Up and Recovery Time Calculator

Check how quickly a calorifier, unvented cylinder or buffer vessel can be brought up to temperature, how much water it can reheat per hour, and what coil or element output you need to meet a required recovery time.

Inputs

Advanced options (3)
%

Results

Heat-up time from cold
121.3
Energy to heat the store
57.62
Recovery rate at this ΔT
494.6
Output needed for target time
60.65

    RefENG-PVH-021
    MethodQ = m·cp·ΔT; time = Q / net heating power
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Mass of waterm = ρ × Vm = 992 × 1 = 992 kg
    2. Energy to heatE = m × cp × ΔTE = 992 × 4,182 × 50 = 207,427 kJ = 57.62 kWh
    3. Heat-up timet = E / (P × efficiency)t = 207,427,200 / (30,000 × 0.95) = 121.3 min
    4. Recovery rateV̇ = P_net / (ρ·cp·ΔT)V̇ = 494.6 L/h raised by 50 K
    5. Output for target timeP = E / (t_target × efficiency)P = 60.65 kW

    Heat-up versus recovery

    Heat-up time is from a full tank of cold water to the set temperature. Recovery rate is how many litres per hour the heater can raise from cold feed to set temperature while water is being drawn off. Both depend only on output and temperature rise, not on the shape of the vessel.

    Legionella control

    Stored hot water is normally kept at 60 °C or above to control Legionella, with distribution at 50 °C or more within a short time at outlets. Check local guidance such as HSG274 in the UK before setting lower temperatures.

    Assumptions and limits

    • Fully mixed store heated as a single mass.
    • Constant heater output; for coils, output falls as the tank warms, so use the output at set temperature.

    References

    • CIBSE Guide G, Public health and plumbing engineering.
    • BS EN 806 and BS 8558, hot water services.
    • HSE HSG274 Part 2, Legionella control in hot and cold water systems.

    Questions

    How long does a 300 L cylinder take to heat with a 3 kW immersion?
    From 10 to 60 °C, about 6 hours (300 kg × 4.18 kJ/kg·K × 50 K ≈ 17.4 kWh).
    Does the coil output stay constant?
    No, a coil delivers less as the store approaches the primary temperature. Use the coil sizing calculator at the set temperature for a conservative figure.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.