Coil Heat Exchanger Sizing Calculator

Size the heating coil for a hot water cylinder, calorifier or process tank. Enter the duty, the primary inlet and outlet temperatures, the tank temperature and an overall U, and the calculator gives the area, tube length, flow rate and velocity in the coil.

Inputs

Advanced options (3)

Results

Total tube length
29.8
Heat transfer area (outside)
2.06
LMTD
18.2
Primary flow rate
1,322
Velocity in coil
1.22

    RefENG-PVH-020
    MethodA = Q / (U·LMTD), LMTD between coil fluid and a well-mixed tank
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Temperature differences to the tankΔT1 = 30 K, ΔT2 = 10 K
    2. LMTDLMTD = (ΔT1 − ΔT2) / ln(ΔT1/ΔT2)LMTD = 18.2 K
    3. Required areaA = Q / (U × LMTD)A = 30,000 / (800 × 18.2) = 2.06 m²
    4. Tube lengthL = A / (π × OD)L = 2.06 / (π × 0.022) = 29.8 m
    5. Primary flow and velocity (m/s)ṁ = Q / (cp·ΔT); v = ṁ/(ρ·n·πID²/4)ṁ = 1,289 kg/h; v = 1.217 m/s

    Design temperature

    Coil output falls as the stored water heats up, because the temperature difference shrinks. Size the coil at the end of the recovery period, with the tank at its set temperature, so it still delivers the duty when it matters most.

    Choosing U

    Heat transfer on the outside of a coil in a storage tank is by natural convection, which limits U. Higher primary velocity, finned or corrugated tube and steam instead of water all raise U. Scale deposits on the outside reduce it over time, so include a margin for hard water.

    Assumptions and limits

    • Well-mixed tank at a single temperature.
    • Area based on the tube outside diameter.
    • Primary fluid properties for hot water unless changed.

    References

    • CIBSE Guide G, Public health and plumbing engineering.
    • Kern, D. Q., Process Heat Transfer, coil heat transfer.

    Questions

    How long a coil do I need for a 300 litre cylinder?
    It depends on the recovery time you want. A 20 to 30 kW coil heated by 80 °C primary water usually needs roughly 15 to 25 m of 22 mm copper tube.
    Can I use this for a steam coil?
    Yes. Set the inlet and outlet close to the steam saturation temperature and use a higher U. Calculate steam flow separately, since the primary flow output assumes sensible heat.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.