Plate Heat Exchanger Sizing Calculator

Plate heat exchangers run close to pure counter-flow, so the effectiveness-NTU method sizes them well. Enter the two flows, their inlet temperatures and the duty you need, and the calculator gives the outlet temperatures, the area and an estimate of the number of plates.

Inputs

Results

Number of plates
15
Required heat transfer area
3.149
Hot outlet temperature
42.27
Cold outlet temperature
53.28
Effectiveness, ε
0.6364
NTU
1.503

    RefENG-PVH-022
    MethodEffectiveness-NTU, counter-flow
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Heat capacity ratesC = ṁ·cpCh = 8,380 W/K, Cc = 10,450 W/K, Cr = 0.8019
    2. Effectiveness requiredε = Q / (Cmin·(Thi − Tci))ε = 400,000 / 628,500 = 0.6364
    3. NTU for counter-flowNTU = ln((ε − 1)/(ε·Cr − 1)) / (Cr − 1)NTU = 1.503
    4. Area and platesA = NTU·Cmin / U; N = A/Ap + 2 end platesA = 3.149 m²; N = 15

    Plate count

    The two end plates do not transfer heat, so they are added to the thermal plates. Manufacturers also choose pass arrangements and plate patterns to balance heat transfer against pressure drop; use this result to compare options before asking for a quotation.

    Close approach

    Plate exchangers can achieve temperature approaches of 1 to 2 °C, which is why they are popular for heat recovery and district heating substations.

    Assumptions and limits

    • Pure counter-flow, single pass.
    • Constant U and specific heats.
    • No phase change.

    References

    • Incropera and DeWitt, Fundamentals of Heat and Mass Transfer, effectiveness-NTU method.
    • Shah, R. K. and Sekulić, D. P., Fundamentals of Heat Exchanger Design.

    Questions

    How many plates do I need for 400 kW?
    It depends on flows, temperatures and U. For example, 2 kg/s of water at 90 °C heating 2.5 kg/s from 15 °C, with U = 4000 W/m²·K, needs about 3.1 m², which is 15 plates of 0.25 m² including the two end plates.
    Why is U so much higher than for shell and tube?
    The corrugated plates create strong turbulence at low velocity, giving high film coefficients on both sides.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.